ASHRAE Standard 241: What It Takes to Meet Clean Air Targets in Offices, Classrooms, and Restaurants

ASHRAE Standard 241 sets clean air targets for infectious aerosols. New simulations show which spaces can meet them, which cannot, and what it takes.

11/27/20266 min read

Four far-UVC germicidal lamps mounted on a stand near the ceiling of a dance hall, used to inactivat
Four far-UVC germicidal lamps mounted on a stand near the ceiling of a dance hall, used to inactivat

Every winter, building owners ask how much a building can do to keep respiratory infections from spreading indoors. ASHRAE's answer is Standard 241, Control of Infectious Aerosols. It sets a measurable target for clean air during periods of elevated disease risk rather than simply recommending more ventilation.

Two developments make this a good moment to look at it again. First, the standard is being revised. The 2023 edition was written on an expedited schedule, and ASHRAE is now taking it through the normal consensus process, with a second public review that closed on November 23, 2026. Second, a 2026 simulation study by Pacific Northwest and Lawrence Berkeley national laboratory researchers tested what it takes to meet the standard's targets. The answer is uneven: easy in offices, demanding in classrooms, and out of reach in some crowded spaces.

What Standard 241 asks a building to do

Standard 241 does not replace normal ventilation rules. A building must still meet ASHRAE 62.1, 62.2, or 170 for everyday operation. Standard 241 adds a second operating state called infection risk management mode, used during identified periods of elevated transmission risk. ASHRAE notes that authorities having jurisdiction can decide when its enhanced protections are required.

In that mode, each occupied space must receive a minimum equivalent clean airflow per person. This is the combined effect of three things: outdoor air, air passed through effective filters, and air treated by devices that inactivate pathogens, such as germicidal ultraviolet (GUV) lamps. The standard is deliberately technology-neutral. A designer can reach the target with any mix of the three, provided each device is rated by an accepted test method.

That rating requirement matters. Mechanical filters must be at least MERV-A 11 or equivalent, and air cleaners must pass safety testing that measures their emissions of ozone, formaldehyde, and particles. A 2024 addendum added further test-method references, including methods that use the MS2 bacteriophage as the challenge organism for UV systems. A device with no credible performance data does not count, however it is marketed.

The standard also requires a building readiness plan. It records how each space will reach its target, how systems will operate in risk mode, and how performance will be verified.

How demanding are the targets?

The targets are much higher than ordinary ventilation rates, and they rise with crowding and vocal activity. Figures from a 2023 presentation on the standard by William Bahnfleth of Penn State show the gap for three common spaces (62.1 default outdoor air rate vs. Standard 241 target, per person):

  • Office: about 17 cfm (8 L/s) under 62.1, compared with 30 cfm (14 L/s) under Standard 241

  • Classroom: about 13 cfm (6 L/s), compared with 40 cfm (19 L/s)

  • Restaurant dining: about 10 cfm (5 L/s), compared with 60 cfm (28 L/s)

Values are doubled for spaces with loud vocalization. The 2023 edition covers 25 space types with targets between 20 and 90 cfm per person.

The per-person framing hides the real difficulty, which is density. Bahnfleth's slides convert the same targets into air changes per hour of clean air for a room with an 8-foot ceiling at default occupancy. An office needs only about 1.1, a classroom about 10.5, and a restaurant about 31.5. Delivering more than 30 air changes of clean air per hour in a dining room is far beyond what typical HVAC systems, or a few portable units, are designed to provide.

For comparison, the U.S. Centers for Disease Control and Prevention suggests aiming for at least 5 air changes per hour of clean air as a rough guide for workplaces. Standard 241 is stricter where people are packed together and more lenient where they are spread out, because it targets a similar level of risk in every covered space.

What the 2026 simulations found

The national laboratory team, publishing in Building and Environment (January 2026), modeled offices, classrooms, restaurant dining areas, and healthcare waiting rooms across seven climate zones using EnergyPlus. Starting from a 62.1 or 170 baseline, they tested more outdoor air, better central filtration, in-duct GUV, portable air cleaners, upper-room GUV, and whole-room GUV, alone and in combination.

The results split cleanly by space type:

  • Offices met the Standard 241 target with a single measure, with minimal effect on energy use and comfort.

  • Classrooms needed either upper-room GUV or a combination such as MERV 13 filtration in the central system plus portable air cleaners.

  • Restaurant dining areas and healthcare waiting rooms could not meet the target at design occupancy, even with several measures combined.

Two assumptions drive the last finding. The researchers used design occupancy, and they used MS2, the test organism the standard specifies for air cleaners, as the challenge agent. Both are conservative, and both are realistic for a compliance calculation.

Our analysis: occupancy is the fourth lever

Most discussion of Standard 241 focuses on equipment. The simulations point to a lever that is easier to overlook. Because the target is set per person, every person removed from a room lowers the clean air the room needs.

The standard allows occupancy in risk mode to differ from design occupancy, and the clean air a space can actually deliver can be used to set a maximum occupancy for that mode. For a crowded dining room or waiting area, a realistic readiness plan may combine the best affordable air-cleaning package with a posted lower occupancy, rather than chasing a target the space cannot physically meet at full capacity.

For new projects, the cheapest time to plan for infection risk mode is before the ceilings close: size air handlers for MERV 13 filters, leave power and mounting points for upper-room GUV in classrooms, and plan where portable units can go. Retrofitting later is far more disruptive.

What owners and designers can do now

  • Check the baseline first. Standard 241 assumes the building already meets current ventilation and filtration standards. Many older buildings do not.

  • Rate what you already have. Outdoor air, filters, and existing air cleaners all count if their performance is documented.

  • Prioritize by space type. Offices are usually straightforward; classrooms deserve early design attention; dense dining, waiting, and assembly spaces need an occupancy strategy.

  • Insist on test data. Count only devices tested by an accepted method and shown safe for ozone and byproducts.

  • Write the readiness plan before you need it. Deciding during an outbreak is much harder.

Standard 241 is a U.S. consensus standard, but its approach of counting clean air per person from all sources is useful anywhere. Projects in Europe and the Middle East can use it voluntarily as a design benchmark.

Conclusion

Standard 241 turns "better air during flu season" into a number that can be designed, measured, and verified. The 2026 simulations show where that number is realistic and where it is not. Offices can comply at little cost. Classrooms can comply with deliberate design. The densest spaces will need both strong air cleaning and limits on occupancy. As the revision moves toward approval, the best-prepared owners will be those who already know how much clean air each space can deliver.

SYNKTECT helps owners and design teams evaluate ventilation, filtration, and air-cleaning options during design optimization and design review and verifies performance through post-occupancy evaluation. Contact us to discuss a readiness plan for your building.

Related reading: ASHRAE Standard 236P: Testing HVAC Control Programming · Indoor Air Quality Policy Is Going Global · Buildings, Thermal Comfort, and Flu Season · Can You Trust Low-Cost Indoor Air Quality Sensors?